05.05 Function diagrams
SIEMENS AG 6RX1700-0AD76 8-43
SIMOREG DC Master Operating Instructions
Sheet G171 USS interface 2
.04
.01
.03
.02
.06
.05
.07
.08
.10
.09
.14
.11
.13
.12
.16
.15
Tx+
Tx-
Rx+/Tx+
Rx-/Tx-
RS485
M
56
57
58
59
60
1
1
M
+
10 10
X172
015
.01
.16
87564321
- G171 -
CUD1
<1>
<1>
[G169.4]
[G182.6]
[G151.3]
[G183.6]
Bit 0 ... Bit 15
P790 (0)
P797 (0,000s)
P796 (0)
P793 (6)
P791 (2)
P792 (127)
r799
P927
1s
B6030
B6031
P798 (6030)
B
K6001
K6002
K6003
K6004
K6005
K6006
K6007
K6008
K6009
K6010
K6011
K6012
K6013
K6014
K6015
K6016
B6100
B6200
B6300
B6400
B6500
B6600
B6700
B6800
B6900
B6115
B6215
B6315
B6415
B6515
B6615
B6715
B6815
B6915
r812.17 r812.18 r812.19 r812.20
r813.17 r813.18 r813.19 r813.20
G-SST2
P795.001 (0)
K
K
K
K
P794
K
K
K
K
K
K
K
K
K
K
K
32
167
0
33
0
0
0
0
0
0
0
0
0
0
0
K
0
U117 (0)
B
B
K6020
r812.01 to .16
USS interface 2
Word 1
Word 2
Word 3
Word 4
Word 5
Word 6
Word 7
Word 8
Word 9
Word 10
Word 1
Word 2
Word 3
Word 4
Word 5
Word 6
Word 7
Word 8
Word 9
Word 10
Process data
to USS interface
Receive data
Transmit data
Word 11
Word 12
Word 13
Word 14
Word 15
Word 16
Word 11
Word 12
Word 13
Word 14
Word 15
Word 16
Word 1: Param.-ID
(PKE)
Word 2: Param.Index
Word 3: Param.Value
Low Word
Word 4: Param.Value
High Word
Parameter
processing
Word 1: Param.-ID
(PKE)
Word 2: Param.Index
Word 3: Param.Value
Low Word
Word 4: Param.Value
High Word
USS parameter data
USS parameter data
Process data
from USS interface
1 = "Fault F012"
Fault message trigger
USS On/Off
Slave address
Baud rate
Length of process data
Length of parameter data
Parameters for USS interface
Telegram monitoring time
USS diagnostic parameter
Enable parameterization
1 = "Telegram
monitoring
timeout"
Bus terminator
every 16 bits
r813.01 to .16
Binector / connector
converter
FS
P795.002=0:
Bit 10 is
not treated as "control by PLC".
P795.002=1:
Bit 10 is treated as "control by PLC",
i.e. when bit 10=0, the other bits of word 1 as well as
words 2 to 16 are
not written to connectors K6001 to K6016
or to binectors B6100 to 6915.
All these connectors and binectors retain their old values.
For transmission of double-word connectors see Section 9.13.1
See also connector type converter on sheet G169