PMCM-9340D-0208 ACCESS 9340 and 9360 Meters
2/2008 Appendix A—Meter Register List
EN–123
1133
Voltage, Unbalance, A-
N
— 0.10%
0 – 1,000
(-32,768 if N/A)
Percent Voltage Unbalance, Phase A-N
4-wire system only
1134
Voltage, Unbalance, B-
N
— 0.10%
0 – 1,000
(-32,768 if N/A)
Percent Voltage Unbalance, Phase B-N
4-wire system only
1135
Voltage, Unbalance, C-
N
— 0.10%
0 – 1,000
(-32,768 if N/A)
Percent Voltage Unbalance, Phase C-N
4-wire system only
1136
Voltage, Unbalance,
Max L-N
— 0.10%
0 – 1,000
(-32,768 if N/A)
Percent Voltage Unbalance, Worst L-N
4-wire system only
1s Metering — Power
1140 Real Power, Phase A F kW/Scale
-32,767 – 32,767
(-32,768 if N/A)
Real Power (PA)
4-wire system only
1141 Real Power, Phase B F kW/Scale
-32,767 – 32,767
(-32,768 if N/A)
Real Power (PB)
4-wire system only
1142 Real Power, Phase C F kW/Scale
-32,767 – 32,767
(-32,768 if N/A)
Real Power (PC)
4-wire system only
1143 Real Power, Total F kW/Scale -32,767 – 32,767
4-wire system = PA+PB+PC
3-wire system = 3-Phase real power
1144
Reactive Power, Phase
A
F kVAr/Scale
-32,767 – 32,767
(-32,768 if N/A)
Reactive Power (QA)
4-wire system only
1145
Reactive Power, Phase
B
F kVAr/Scale
-32,767 – 32,767
(-32,768 if N/A)
Reactive Power (QB)
4-wire system only
1146
Reactive Power, Phase
C
F kVAr/Scale
-32,767 – 32,767
(-32,768 if N/A)
Reactive Power (QC)
4-wire system only
1147 Reactive Power, Total F kVAr/Scale -32,767 – 32,767
4-wire system = QA+QB+QC
3 wire system = 3-Phase reactive power
1148
Apparent Power,
Phase A
F kVA/Scale
-32,767 – 32,767
(-32,768 if N/A)
Apparent Power (SA)
4-wire system only
1149
Apparent Power,
Phase B
F kVA/Scale
-32,767 – 32,767
(-32,768 if N/A)
Apparent Power (SB)
4-wire system only
1150
Apparent Power,
Phase C
F kVA/Scale
-32,767 – 32,767
(-32,768 if N/A)
Apparent Power (SC)
4-wire system only
1151 Apparent Power, Total F kVA/Scale -32,767 – 32,767
4-wire system = SA+SB+SC
3-wire system = 3-Phase apparent power
1s Metering — Power Factor
1160
True Power Factor,
Phase A
— 0.001
-0.002 to 1.000
to +0.002
(-32,768 if N/A)
Derived using the complete harmonic content
of real and apparent power.
4-wire system only
1161
True Power Factor,
Phase B
— 0.001
-0.002 to 1.000
to +0.002
(-32,768 if N/A)
Derived using the complete harmonic content
of real and apparent power.
4-wire system only
Table A–3: Abbreviated Register List
Reg Name Scale Units Range Notes