© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Appendix A—Meter Register List 2/2008
EN–124
1162
True Power Factor,
Phase C
0.001
-0.002 to 1.000
to +0.002
(-32,768 if N/A)
Derived using the complete harmonic content
of real and apparent power.
4-wire system only
1163
True Power Factor,
Total
0.001
-0.002 to 1.000
to +0.002
(-32,768 if N/A)
Derived using the complete harmonic content
of real and apparent power
1164
Alternate True Power
Factor, Phase A
0.001
0 – 2,000
(-32,768 if N/A)
Derived using the complete harmonic content
of real and apparent power (4-wire system
only). The reported value is mapped from 0-
2000, with 1000 representing unity, values
below 1000 representing lagging, and values
above 1000 representing leading.
1165
Alternate True Power
Factor, Phase B
0.001
0 – 2,000
(-32,768 if N/A)
Derived using the complete harmonic content
of real and apparent power (4-wire system
only). The reported value is mapped from 0-
2000, with 1000 representing unity, values
below 1000 representing lagging, and values
above 1000 representing leading
.
1166
Alternate True Power
Factor, Phase C
0.001
0 – 2,000
(-32,768 if N/A)
Derived using the complete harmonic content
of real and apparent power (4-wire system
only). The reported value is mapped from 0-
2000, with 1000 representing unity, values
below 1000 representing lagging, and values
above 1000 representing leading.
1167
Alternate True Power
Factor, Total
0.001 0 – 2,000
Derived using the complete harmonic content
of real and apparent power. The reported value
is mapped from 0-2000, with 1000 representing
unity, values below 1000 representing lagging,
and values above 1000 representing leading.
1168
Displacement Power
Factor, Phase A
0.001
-0.002 to 1.000
to +0.002
(-32,768 if N/A)
Derived using only fundamental frequency of
the real and apparent power.
4-wire system only
1169
Displacement Power
Factor, Phase B
0.001
-0.002 to 1.000
to +0.002
(-32,768 if N/A)
Derived using only fundamental frequency of
the real and apparent power.
4-wire system only
1170
Displacement Power
Factor, Phase C
0.001
-0.002 to 1.000
to +0.002
(-32,768 if N/A)
Derived using only fundamental frequency of
the real and apparent power.
4-wire system only
1171
Displacement Power
Factor, Total
0.001
-0.002 to 1.000
to +0.002
(-32,768 if N/A)
Derived using only fundamental frequency of
the real and apparent power
1172
Alternate Displacement
Power Factor, Phase A
0.001
0 – 2,000
(-32,768 if N/A)
Derived using only fundamental frequency of
the real and apparent power (4-wire system
only). The reported value is mapped from 0-
2000, with 1000 representing unity, values
below 1000 representing lagging, and values
above 1000 representing leading.
Table A3: Abbreviated Register List
Reg Name Scale Units Range Notes