© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
PMCM-9340D-0208 ACCESS 9340 and 9360 Meters
2/2008 Appendix A—Meter Register List
EN–125
1173
Alternate Displacement
Power Factor, Phase B
— 0.001
0 – 2,000
(-32,768 if N/A)
Derived using only fundamental frequency of
the real and apparent power (4-wire system
only). The reported value is mapped from 0-
2000, with 1000 representing unity, values
below 1000 representing lagging, and values
above 1000 representing leading.
1174
Alternate Displacement
Power Factor, Phase C
— 0.001
0 – 2,000
(-32,768 if N/A)
Derived using only fundamental frequency of
the real and apparent power (4-wire system
only). The reported value is mapped from 0-
2000, with 1000 representing unity, values
below 1000 representing lagging, and values
above 1000 representing leading.
1175
Alternate Displacement
Power Factor, Total
— 0.001 0 – 2,000
Derived using only fundamental frequency of
the real and apparent power. The reported
value is mapped from 0-2000, with 1000
representing unity, values below 1000
representing lagging, and values above 1000
representing leading.
1s Metering — Frequency
1180 Frequency —
0.01Hz
0.10Hz
(50/60Hz)
2,300 – 6,700
(400Hz)
3,500 – 4,500
(-32,768 if N/A)
Frequency of circuits being monitored. If the
frequency is out of range, the register is -
32,768.
Power Quality
THD
1200
THD/thd Current,
Phase A
— 0.10% 0 – 32,767
Total Harmonic Distortion, Phase A Current
See register 3227 for THD/ thd definition
1201
THD/thd Current,
Phase B
— 0.10% 0 – 32,767
Total Harmonic Distortion, Phase B Current
See register 3227 for THD/ thd definition
1202
THD/thd Current,
Phase C
— 0.10% 0 – 32,767
Total Harmonic Distortion, Phase C Current
See register 3227 for THD/ thd definition
1203
THD/thd Current,
Phase N
— 0.10%
0 – 32,767
(-32,768 if N/A)
Total Harmonic Distortion, Phase N Current
(4-wire system only)
See register 3227 for THD/ thd definition
1207
THD/thd Voltage,
Phase A-N
— 0.10%
0 – 32,767
(-32,768 if N/A)
Total Harmonic Distortion Phase A-N
(4-wire system only)
See register 3227 for THD/ thd definition
1208
THD/thd Voltage,
Phase B-N
— 0.10%
0 – 32,767
(-32,768 if N/A)
Total Harmonic Distortion Phase B-N
(4-wire system only)
See register 3227 for THD/ thd definition
1209
THD/thd Voltage,
Phase C-N
— 0.10%
0 – 32,767
(-32,768 if N/A)
Total Harmonic Distortion Phase C-N
(4-wire system only)
See register 3227 for THD/ thd definition
Table A–3: Abbreviated Register List
Reg Name Scale Units Range Notes