© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Appendix A—Meter Register List 2/2008
EN–126
1211
THD/thd Voltage,
Phase A-B
— 0.10% 0 – 32,767
Total Harmonic Distortion Phase A-B
See register 3227 for THD/ thd definition
1212
THD/thd Voltage,
Phase B-C
— 0.10% 0 – 32,767
Total Harmonic Distortion Phase B-C
See register 3227 for THD/ thd definition
1213
THD/thd Voltage,
Phase C-A
— 0.10% 0 – 32,767
Total Harmonic Distortion Phase C-A
See register 3227 for THD/ thd definition
Fundamental Magnitudes and Angles
Current
1230
Current Fundamental
RMS Magnitude,
Phase A
A Amps/Scale 0 – 32,767
1231
Current Fundamental
Coincident Angle,
Phase A
— 0.1° 0 – 3,599 Referenced to A-N/A-B Voltage Angle
1232
Current Fundamental
RMS Magnitude,
Phase B
A Amps/Scale 0 – 32,767
1233
Current Fundamental
Coincident Angle,
Phase B
— 0.1° 0 – 3,599 Referenced to A-N/A-B Voltage Angle
1234
Current Fundamental
RMS Magnitude,
Phase C
A Amps/Scale 0 – 32,767
1235
Current Fundamental
Coincident Angle,
Phase C
— 0.1° 0 – 3,599 Referenced to A-N/A-B Voltage Angle
1236
Current Fundamental
RMS Magnitude,
Neutral
B Amps/Scale
0 – 32,767
(-32,768 if N/A)
4-wire system only
1237
Current Fundamental
Coincident Angle,
Neutral
— 0.1°
0 – 3,599
(-32,768 if N/A)
Referenced to A-N
4-wire system only
Voltage
1244
Voltage Fundamental
RMS Magnitude, A-
N/A-B
D Volts/Scale 0 – 32,767
Voltage A-N (4-wire system)
Voltage A-B (3-wire system)
1245
Voltage Fundamental
Coincident Angle, A-
N/A-B
— 0.1° 0 – 3,599 Referenced to A-N (4-wire) or A-B (3-wire)
1246
Voltage Fundamental
RMS Magnitude, B-
N/B-C
D Volts/Scale 0 – 32,767
Voltage B-N (4-wire system)
Voltage B-C (3-wire system)
1247
Voltage Fundamental
Coincident Angle, B-
N/B-C
— 0.1° 0 – 3,599 Referenced to A-N (4-wire) or A-B (3-wire)
1248
Voltage Fundamental
RMS Magnitude, C-
N/C-A
D Volts/Scale 0 – 32,767
Voltage C-N (4-wire system)
Voltage C-A (3-wire system)
Table A–3: Abbreviated Register List