PMCM-9340D-0208 ACCESS 9340 and 9360 Meters
2/2008 Appendix A—Meter Register List
EN–131
1776
Energy, Incremental
Reactive Out, Present
Interval
VArH (3)
3-Phase total accumulated incremental
reactive energy out of the load
1779
Energy, Incremental
Apparent, Present
Interval
VAH (3)
3-Phase total accumulated incremental
apparent energy
1782
Energy, Reactive,
Quadrant 1
VArH (3)
3-Phase total accumulated incremental
reactive energy – quadrant 1
1785
Energy, Reactive,
Quadrant 2
VArH (3)
3-Phase total accumulated incremental
reactive energy – quadrant 2
1788
Energy, Reactive,
Quadrant 3
VArH (3)
3-Phase total accumulated incremental
reactive energy – quadrant 3
1791
Energy, Reactive,
Quadrant 4
VArH (3)
3-Phase total accumulated incremental
reactive energy – quadrant 4
1794
Conditional Energy
Control Status
0 – 1
0 = Off (default)
1 = On
(1) 0 – 9,999,999,999,999,999
(2) -9,999,999,999,999,999 – 9,999,999,999,999,999
(3) 0 – 999,999,999,999
Demand
Demand — Current Demand System Configuration and Data
1800
Demand Calculation
Mode
Current
0 – 1024
0 = Thermal Demand (default)
1 = Timed Interval Sliding Block
2 = Timed Interval Block
4 = Timed Interval Rolling Block
8 = Input Synchronized Block
16 = Input Synchronized Rolling Block
32 = Command Synchronized Block
64 = Command Synchronized Rolling Block
128 = Clock Synchronized Block
256 = Clock Synchronized Rolling Block
512 = Slave to Power Demand Interval
1024 = Slave to Incremental Energy Interval
1801
Demand Interval
Current
Minutes 1 – 60 Default = 15
1802
Demand Subinterval
Current
Minutes 1 – 60 Default = 1
1803
Demand Sensitivity
Current
1% 1 – 99
Adjusts the sensitivity of the thermal demand
calculation. Default = 90
1805
Short Demand Interval
Current
Seconds 0 – 60
Sets the interval for a running average demand
calculation of short duration. Default = 15
1806
Time Elapsed in
Interval
Current
Seconds 0 – 3,600 Time elapsed in the present demand interval.
Table A3: Abbreviated Register List