ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Appendix A—Meter Register List 2/2008
EN–132
1807
Time Elapsed in
Subinterval
Current
Seconds 0 – 3,600
Time elapsed in the present demand
subinterval.
1808
Interval Count
Current
1.0 0 – 32,767
Count of demand intervals. Rolls over at
32,767.
1809
Subinterval Count
Current
1.0 0 – 60
Count of demand subintervals. Rolls over at
interval.
1810
Min/Max Reset
DateTime
Current
Table A1
on page 121
Table A1
on page 121
Date/Time of last reset of Current Demand
Min/Max demands
1814
Min/Max Reset Count
Current
1.0 0 – 32,767
Count of Min/Max demand resets. Rolls over at
32,767.
1815
Demand System
Status
Current
0x0000 – 0x000F
Bit 00 = end of demand subinterval
Bit 01 = end of demand interval
Bit 02 = start of first complete interval
Bit 03 = end of first complete interval
Demand — Power Demand System Configuration and Data
1840
Demand Calculation
Mode
Power
0 – 1024
0 = Thermal Demandlt)
1 = Timed Interval Sliding Block
2 = Timed Interval Block
4 = Timed Interval Rolling Block
8 = Input Synchronized Block
16 = Input Synchronized Rolling Block
32 = Command Synchronized Block
64 = Command Synchronized Rolling Block
128 = Clock Synchronized Block
256 = Clock Synchronized Rolling Block
1024 = Slave to Incremental Energy Interval
1841
Demand Interval
Power
Minutes 1 – 60 Default = 15
1842
Demand Subinterval
Power
Minutes 1 – 60 Default = 1
1843
Demand Sensitivity
Power
1% 1 – 99
Adjusts the sensitivity of the thermal demand
calculation. Default = 90
1844
Predicted Demand
Sensitivity
Power
1.0 1 – 10
Adjusts sensitivity of predicted demand
calculation to recent changes in power
consumption. Default = 5.
1845
Short Demand Interval
Power
Seconds 0 – 60
Sets the interval for a running average demand
calculation of short duration. Default = 15
1846
Time Elapsed in
Interval
Power
Seconds 0 – 3,600 Time elapsed in the present demand interval.
Table A3: Abbreviated Register List