PMCM-9340D-0208 ACCESS 9340 and 9360 Meters
2/2008 Appendix A—Meter Register List
EN–133
1847
Time Elapsed in
Subinterval
Power
Seconds 0 – 3,600
Time elapsed in the present demand
subinterval.
1848
Interval Count
Power
1.0 0 – 32,767
Count of demand intervals. Rolls over at
32,767.
1849
Subinterval Count
Power
1.0 0 – 60
Count of demand subintervals. Rolls over at
interval.
1850
Min/Max Reset
DateTime
Power
Table A1
on page 121
Table A1
on page 121
Date/Time of last reset of Power Demand
Min/Max demands
1854
Min/Max Reset Count
Power
1.0 0 – 32,767
Count of Min/Max demand resets. Rolls over at
32,767.
1855
Demand System
Status
Power
0x0000 – 0x000F
Bit 00 = end of demand subinterval
Bit 01 = end of demand interval
Bit 02 = start of first complete interval
Bit 03 = end of first complete interval
Demand — Input Metering Demand System Configuration and Data
1860
Demand Calculation
Mode
Input Pulse Metering
0 – 1024
0 = Thermal Demand
1 = Timed Interval Sliding Block
2 = Timed Interval Block (default)
4 = Timed Interval Rolling Block
8 = Input Synchronized Block
16 = Input Synchronized Rolling Block
32 = Command Synchronized Block
64 = Command Synchronized Rolling Block
128 = Clock Synchronized Block
256 = Clock Synchronized Rolling Block
512 = Slave to Power Demand Interval
1024 = Slave to Incremental Energy Interval
1861
Demand Interval
Input Pulse Metering
Minutes 1 – 60 Default = 15
1862
Demand Subinterval
Input Pulse Metering
Minutes 1 – 60 Default = 1
1863
Demand Sensitivity
Input Pulse Metering
1% 1 – 99
Adjusts the sensitivity of the thermal demand
calculation. Default = 90
1865
Short Demand Interval
Input Pulse Metering
Seconds 0 – 60
Sets the interval for a running average demand
calculation of short duration. Default = 15
1866
Time Elapsed in
Interval
Input Pulse Metering
Seconds 0 – 3,600
1867
Time Elapsed in
Subinterval
Input Pulse Metering
Seconds 0 – 3,600