© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Appendix A—Meter Register List 2/2008
EN–134
1868
Interval Count
Input Pulse Metering
— 1.0 0 – 32,767 Rolls over at 32,767.
1869
Subinterval Count
Input Pulse Metering
— 1.0 0 – 60 Rolls over at interval.
1870
Min/Max Reset
DateTime
Input Pulse Metering
—
Table A–1
on page 121
Table A–1
on page 121
1874
Min/Max Reset Count
Input Pulse Metering
— 1.0 0 – 32,767 Rolls over at 32,767.
1875
Demand System
Status
Input Pulse Metering
— — 0x0000 – 0x000F
Bit 00 = end of demand subinterval
Bit 01 = end of demand interval
Bit 02 = start of first complete interval
Bit 03 = end of first complete interval
Demand — Generic Demand System Configuration and Data
1880
Demand Calculation
Mode
Generic Group 1
— — 0 – 1024
0 = Thermal Demand (default)
1 = Timed Interval Sliding Block
2 = Timed Interval Block
4 = Timed Interval Rolling Block
8 = Input Synchronized Block
16 = Input Synchronized Rolling Block
32 = Command Synchronized Block
64 = Command Synchronized Rolling Block
128 = Clock Synchronized Block
256 = Clock Synchronized Rolling Block
512 = Slave to Power Demand Interval
1024 = Slave to Incremental Energy Interval
1881
Demand Interval
Generic
— Minutes 1 – 60 Default = 15
1882
Demand Subinterval
Generic
— Minutes 1 – 60 Default = 1
1883
Demand Sensitivity
Generic
— 1% 1 – 99
Adjusts the sensitivity of the thermal demand
calculation. Default = 90
1885
Short Demand Interval
Generic
— Seconds 0 – 60
Sets the interval for a running average demand
calculation of short duration. Default = 15
1886
Time Elapsed in
Interval
Generic
— Seconds 0 – 3,600 Time elapsed in the present demand interval.
1887
Time Elapsed in
Subinterval
Generic
— Seconds 0 – 3,600
Time elapsed in the present demand
subinterval.
1888
Interval Count
Generic
— 1.0 0 – 32,767
Count of demand intervals. Rolls over at
32,767.
Table A–3: Abbreviated Register List
Reg Name Scale Units Range Notes