© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Appendix A—Meter Register List 2/2008
EN–136
Demand — Current Demand Channels
1960
Last Demand
Current, Phase A
A Amps/Scale 0 – 32,767 Phase A current demand, last complete interval
1961
Present Demand
Current, Phase A
A Amps/Scale 0 – 32,767 Phase A current demand, present interval
1962
Running Average
Demand
Current, Phase A
A Amps/Scale 0 – 32,767
Phase A current demand, running average
demand calculation of short duration
1963
Peak Demand
Current, Phase A
A Amps/Scale 0 – 32,767 Phase A peak current demand
1964
Peak Demand
DateTime
Current, Phase A
—
Table A–1
on page 121
Table A–1
on page 121
Date/Time of Peak Current Demand, Phase A
1970
Last Demand
Current, Phase B
A Amps/Scale 0 – 32,767 Phase B current demand, last complete interval
1971
Present Demand
Current, Phase B
A Amps/Scale 0 – 32,767 Phase B current demand, present interval
1972
Running Average
Demand
Current, Phase B
A Amps/Scale 0 – 32,767
Phase B current demand, running average
demand calculation of short duration
1973
Peak Demand
Current Phase B
A Amps/Scale 0 – 32,767 Phase B peak current demand
1974
Peak Demand
DateTime
Current Phase B
—
Table A–1
on page 121
Table A–1
on page 121
Date/Time of Peak Current Demand, Phase B
1980
Last Demand
Current, Phase C
A Amps/Scale 0 – 32,767
Phase C current demand, last complete
interval
1981
Present Demand
Current, Phase C
A Amps/Scale 0 – 32,767 Phase C current demand, present interval
1982
Running Average
Demand
Current, Phase C
A Amps/Scale 0 – 32,767
Phase C current demand, running average
demand calculation of short duration
1983
Peak Demand
Current Phase C
A Amps/Scale 0 – 32,767 Phase C peak current demand
1984
Peak Demand
DateTime
Current Phase C
—
Table A–1
on page 121
Table A–1
on page 121
Date/Time of Peak Current Demand, Phase C
1990
Last Demand
Current, Neutral
A Amps/Scale
0 – 32,767
(-32,768 if N/A)
Neutral current demand, last complete interval
4-wire system only
1991
Present Demand
Current, Neutral
A Amps/Scale
0 – 32,767
(-32,768 if N/A)
Neutral current demand, present interval
4-wire system only
Table A–3: Abbreviated Register List