© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Appendix A—Meter Register List 2/2008
EN–138
2159
Cumulative Demand
Real Power, 3-Phase
Total
F kW/Scale
-2147483648 –
2147483647
2161
Power Factor, Average
@ Peak Demand, Real
Power
0.001
1,000
-100 to 100
(-32,768 if N/A)
Average True Power Factor at the time of the
Peak Real Demand
2162
Power Demand,
Reactive @ Peak
Demand, Real Power
F kVAr/Scale -32,767 – 32,767
Reactive Power Demand at the time of the
Peak Real Demand
2163
Power Demand,
Apparent @ Peak
Demand, Real Power
F kVA/Scale 0 – 32,767
Apparent Power Demand at the time of the
Peak Real Demand
2165
Last Demand
Reactive Power, 3-
Phase Total
F kVAr /Scale -32,767 – 32,767
3-Phase total present reactive power demand
for last completed demand interval – updated
every sub-interval
2166
Present Demand
Reactive Power, 3-
Phase Total
F kVAr /Scale -32,767 – 32,767
3-Phase total present real power demand for
present demand interval
2167
Running Average
Demand
Reactive Power, 3-
Phase Total
F kVAr /Scale -32,767 – 32,767
3-Phase total present reactive power demand,
running average demand calculation of short
duration – updated every second
2168
Predicted Demand
Reactive Power, 3-
Phase Total
F kVAr /Scale -32,767 – 32,767
Predicted reactive power demand at the end of
the present interval
2169
Peak Demand
Reactive Power, 3-
Phase Total
F kVAr /Scale -32,767 – 32,767
2170
Peak Demand
DateTime
Reactive Power, 3-
Phase Total
Table A1
on page 121
Table A1
on page 121
2174
Cumulative Demand
Reactive Power, 3-
Phase Total
F kVAr /Scale
-2147483648 –
2147483647
2176
Power Factor, Average
@ Peak Demand,
Reactive Power
0.001
1,000
-100 to 100
(-32,768 if N/A)
Average True Power Factor at the time of the
Peak Reactive Demand
2177
Power Demand, Real
@
Peak Demand,
Reactive Power
F kW/Scale -32,767 – 32,767
Real Power Demand at the time of the Peak
Reactive Demand
2178
Power Demand,
Apparent @ Peak
Demand, Reactive
Power
F kVA/Scale 0 – 32,767
Apparent Power Demand at the time of the
Peak Reactive Demand
Table A3: Abbreviated Register List
Reg Name Scale Units Range Notes