2/2008 Appendix A—Meter Register List
EN–139
2180
Last Demand
Apparent Power 3-
Phase Total
F kVA /Scale -32,767 – 32,767
3-Phase total present apparent power demand
for last completed demand interval – updated
every sub-interval
2181
Present Demand
Apparent Power, 3-
Phase Total
F kVA /Scale -32,767 – 32,767
3-Phase total present apparent power demand
for present demand interval
2182
Running Average
Demand
Apparent Power, 3-
Phase Total
F kVA /Scale -32,767 – 32,767
3-Phase total present apparent power demand,
running average demand calculation of short
duration – updated every second
2183
Predicted Demand
Apparent Power, 3-
Phase Total
F kVA /Scale -32,767 – 32,767
Predicted apparent power demand at the end
of the present interval
2184
Peak Demand
Apparent Power, 3-
Phase Total
F kVA /Scale -32,767 – 32,767
3-Phase total peak apparent power demand
peak
2185
Peak Demand
DateTime
Apparent Power, 3-
Phase Total
Table A1
on page 121
Table A1
on page 121
Date/Time of 3-Phase peak apparent power
demand
2189
Cumulative Demand
Apparent Power, 3-
Phase Total
F kVA /Scale
-2,147,483,648 –
2,147,483,647
Cumulative Demand, Apparent Power
2191
Power Factor, Average
@ Peak Demand,
Apparent Power
0.001
1,000
-100 to 100
(-32,768 if N/A)
Average True Power Factor at the time of the
Peak Apparent Demand
2192
Power Demand, Real
@ Peak Demand,
Apparent Power
F kW/Scale -32,767 – 32,767
Real Power Demand at the time of the Peak
Apparent Demand
2193
Power Demand,
Reactive @ Peak
Demand, Apparent
Power
F kVAr/Scale 0 – 32,767
Reactive Power Demand at the time of the
Peak Apparent Demand
Demand — Input Metering Demand Channels
2200
Consumption Units
Code
Input Channel #1
See Unit Codes
Units in which consumption is to be
accumulated
Default = 0
2201
Demand Units Code
Input Channel #1
See Unit Codes
Units in which demand (rate) is to be
expressed
Default = 0
2202
Last Demand
Input Channel #1
0 – 32,767
Last complete interval, updated every sub-
interval
2203
Present Demand
Input Channel #1
0 – 32,767 Present interval
Table A3: Abbreviated Register List