ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Appendix A—Meter Register List 2/2008
EN–140
2204
Running Average
Demand
Input Channel #1
0 – 32,767
Running average demand calculation of short
duration, updated every second
2205
Peak Demand
Input Channel #1
0 – 32,767
2206
Peak Demand
Date/Time
Input Channel #1
Table A1
on page 121
Table A1
on page 121
2210
Minimum Demand
Input Channel #1
0 – 32,767
2211
Minimum Demand
Date/Time
Input Channel #1
Table A1
on page 121
Table A1
on page 121
2215
Cumulative Usage
Input Channel #1
(2) (1)
The user must identify the units to be used in
the accumulation.
2220 Input Channel #2
Same as registers 2200 – 2219 except for
Channel #2
2240 Input Channel #3
Same as registers 2200 – 2219 except for
Channel #3
2260 Input Channel #4
Same as registers 2200 – 2219 except for
Channel #4
2280 Input Channel #5
Same as registers 2200 – 2219 except for
Channel #5
Demand — Generic Group 1 Demand Channels
2400
Input Register
Generic Channel #1
Register selected for generic demand
calculation
2401
Unit Code
Generic Channel #1
-32,767 – 32,767 Used by software
2402
Scale Code
Generic Channel #1
-3 – 3
2403
Last Demand
Generic Channel #1
0 – 32,767
2404
Present Demand
Generic Channel #1
0 – 32,767
2405
Running Average
Demand
Generic Channel #1
0 – 32,767 Updated every second
2406
Peak Demand
Generic Channel #1
0 – 32,767
Table A3: Abbreviated Register List