© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
PMCM-9340D-0208 ACCESS 9340 and 9360 Meters
2/2008 Appendix A—Meter Register List
EN–141
2407
Peak Demand
Date/Time
Generic Channel #1
—
Table A–1
on page 121
Table A–1
on page 121
2411
Minimum Demand
Generic Channel #1
— — 0 – 32,767
2412
Minimum Demand
Date/Time
Generic Channel #1
—
Table A–1
on page 121
Table A–1
on page 121
2420 Generic Channel #2
Same as registers 2400 – 2419 except for
Channel #2
2440 Generic Channel #3
Same as registers 2400 – 2419 except for
Channel #3
2460 Generic Channel #4
Same as registers 2400 – 2419 except for
Channel #4
2480 Generic Channel #5
Same as registers 2400 – 2419 except for
Channel #5
2500 Generic Channel #6
Same as registers 2400 – 2419 except for
Channel #6
2520 Generic Channel #7
Same as registers 2400 – 2419 except for
Channel #7
2540 Generic Channel #8
Same as registers 2400 – 2419 except for
Channel #8
2560 Generic Channel #9
Same as registers 2400 – 2419 except for
Channel #9
2580 Generic Channel #10
Same as registers 2400 – 2419 except for
Channel #10
Phase Extremes
2800
Current, Highest Phase
Value
A Amps/Scale 0 – 32,767 Highest value of Phases A, B, C or N
2801
Current, Lowest Phase
Value
A Amps/Scale 0 – 32,767 Lowest value of Phases A, B, C or N
2802
Voltage, L-L, Highest
Value
D Volts/Scale 0 – 32,767 Highest value of Phases A-B, B-C or C-A
2803
Voltage, L-L, Lowest
Value
D Volts/Scale 0 – 32,767 Lowest value of Phases A-B, B-C or C-A
2804
Voltage, L-N, Highest
Value
D Volts/Scale
0 – 32,767
(-32,768 if N/A)
Highest value of Phases A-N, B-N or C-N
4-wire system only
2805
Voltage, L-N, Lowest
Value
D Volts/Scale
0 – 32,767
(-32,768 if N/A)
Lowest value of Phases A-N, B-N or C-N
4-wire system only
System Configuration
3002 Meter Nameplate — — —
3014
Meter Present
Operating System
Firmware Revision
Level
— —
0x0000 –
0xFFFF
Table A–3: Abbreviated Register List
Reg Name Scale Units Range Notes