ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Appendix A—Meter Register List 2/2008
EN–152
Communications
Communications — RS485
3400 Protocol — — 0 – 2
0 = Modbus (default)
1 = Jbus
3401 Address — — 0 – 255
Valid Addresses: (Default = 1)
Modbus: 0 – 247
Jbus: 0 – 255
3402 Baud Rate — — 0 – 5
3 = 9600 (default)
4 = 19200
5 = 38400
3403 Parity — — 0 – 2
0 = Even (default)
1 = Odd
2 = None
3410 Packets To This Unit — — 0 – 32,767
Number of valid messages addressed to this
unit
3411 Packets To Other Units — — 0 – 32,767
Number of valid messages addressed to other
units
3412
Packets With Invalid
Address
— — 0 – 32,767
Number of messages received with invalid
address
3413 Packets With Bad CRC — — 0 – 32,767 Number of messages received with bad CRC
3414 Packets With Error — — 0 – 32,767 Number of messages received with errors
3415
Packets With Illegal
Opcode
— — 0 – 32,767
Number of messages received with an illegal
opcode
3416
Packets With Illegal
Register
— — 0 – 32,767
Number of messages received with an illegal
register
3417
Invalid Write
Responses
— — 0 – 32,767 Number of invalid write responses
3418
Packets With Illegal
Counts
— — 0 – 32,767
Number of messages received with an illegal
count
3419
Packets With Frame
Error
— — 0 – 32,767
Number of messages received with a frame
error
3420 Broadcast Messages — — 0 – 32,767 Number of broadcast messages received
3421 Number Of Exceptions — — 0 – 32,767 Number of exception replies
3422
Messages With Good
CRC
— — 0 – 32,767
Number of messages received with a good
CRC
3423 Modbus Event Counter — — 0 – 32,767 Modbus Event Counter
Table A–3: Abbreviated Register List
Reg Name Scale Units Range Notes