© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
PMCM-9340D-0208 ACCESS 9340 and 9360 Meters
2/2008 Appendix A—Meter Register List
EN–151
3262 Phase Loss Bitmap — Binary
0x0000 – 0x007F
(-32,768 if N/A)
0 = OK
1 = Phase Loss
Bit 00 = Summary Bit (On if any other bit is on)
Bit 01 = Voltage Phase A
Bit 02 = Voltage Phase B
Bit 03 = Voltage Phase C
Bit 04 = Current Phase A
Bit 05 = Current Phase B
Bit 06 = Current Phase C
This register is controlled by the voltage and
current phase loss alarms. These alarms must
be configured and enabled for this register to
be populated.
Metering Configuration and Status — Resets
3266
Previous Month
Minimum/Maximum
Start Date/Time
—
Table A–1
on page 121
Table A–1
on page 121
3270
Present Month
Minimum/Maximum
Reset Date/Time
—
Table A–1
on page 121
Table A–1
on page 121
3274
Accumulated Energy
Reset
Date/Time
—
Table A–1
on page 121
Table A–1
on page 121
3278
Conditional Energy
Reset
Date/Time
—
Table A–1
on page 121
Table A–1
on page 121
3282
Incremental Energy
Reset
Date/Time
—
Table A–1
on page 121
Table A–1
on page 121
3286
Input Metering
Accumulation Reset
Date/Time
—
Table A–1
on page 121
Table A–1
on page 121
3290
Accumulated Energy
Preset
Date/Time
—
Table A–1
on page 121
Table A–1
on page 121
Table A–3: Abbreviated Register List
Reg Name Scale Units Range Notes