3260
Wiring Error Detection
4
— Binary
0x0000 –
0xFFFF
0 = Normal
1 = Error
Bit 00 = CTa reversed polarity
Bit 01 = CTb reversed polarity
Bit 02 = CTc reversed polarity
Bit 03 = Reserved
Bit 04 = Move CTa to CTb
Bit 05 = Move CTb to CTc
Bit 06 = Move CTc to Cta
Bit 07 = Move CTa to CTc
Bit 08 = Move CTb to Cta
Bit 09 = Move CTc to CTb
Bit 10 = Move CTa to CTb & reverse polarity
Bit 11 = Move CTb to CTc & reverse polarity
Bit 12 = Move CTc to CTa & reverse polarity
Bit 13 = Move CTa to CTc & reverse polarity
Bit 14 = Move CTb to CTa & reverse polarity
Bit 15 = Move CTc to CTb & reverse polarity
3261 Scaling Error — Binary 0x0000 – 0x003F
Indicates potential over range due to scaling
error
0 = Normal
1 = Error
Bit 00 = Summary Bit (On if any other bit is on)
Bit 01 = Scale A – Phase Current Error
Bit 02 = Scale B – Neutral Current Error
Bit 03 = Unused
Bit 04 = Scale D – Phase Voltage Error
Bit 05 = Scale E – Neutral Voltage Error
Bit 06 = Scale F – Power Error
Table A–3: Abbreviated Register List
Reg Name Scale Units Range Notes