PMCM-9340D-0208 ACCESS 9340 and 9360 Meters
2/2008 Appendix A—Meter Register List
EN–149
3258
Wiring Error Detection
2
Binary
0x0000 –
0xFFFF
0 = Normal
1 = Error
Bit 00 = Van magnitude error
Bit 01 = Vbn magnitude error
Bit 02 = Vcn magnitude error
Bit 03 = Vab magnitude error
Bit 04 = Vbc magnitude error
Bit 05 = Vca magnitude error
Bit 06 = Van angle not as expected
Bit 07 = Vbn angle not as expected
Bit 08 = Vcn angle not as expected
Bit 09 = Vab angle not as expected
Bit 10 = Vbc angle not as expected
Bit 11 = Vca angle not as expected
Bit 12 = Vbn is reversed polarity
Bit 13 = Vcn is reversed polarity
Bit 14 = Vbc is reversed polarity
Bit 15 = Vca is reversed polarity
3259
Wiring Error Detection
3
Binary
0x0000 –
0xFFFF
0 = Normal
1 = Error
Bit 00 = Move VTa to VTb
Bit 01 = Move VTb to VTc
Bit 02 = Move VTc to VTa
Bit 03 = Move VTa to VTc
Bit 04 = Move VTb to VTa
Bit 05 = Move VTc to VTb
Bit 06 = Reserved
Bit 07 = Reserved
Bit 08 = Reserved
Bit 09 = Reserved
Bit 10 = Ia is < 1% of CT
Bit 11 = Ib is < 1% of CT
Bit 12 = Ic is < 1% of CT
Bit 13 = Ia angle not in expected range
Bit 14 = Ib angle not in expected range
Bit 15 = Ic angle not in expected range
Table A3: Abbreviated Register List
Reg Name Scale Units Range Notes