© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Appendix A—Meter Register List 2/2008
EN–148
Metering Configuration and Status — Diagnostics
3254
Metering System
Diagnostic Summary
— Binary
0x0000 –
0xFFFF
0 = Normal
1 = Error
Bit 00 = Summary Bit (On if any other bit is on)
Bit 01 = Configuration Error
Bit 02 = Scaling Error
Bit 03 = Phase Loss
Bit 04 = Wiring Error
Bit 05 = Incremental Energy may be incorrect
due to meter reset
Bit 06 = External Demand Sync Timeout
3255
Metering System
Configuration Error
Summary
— Binary
0x0000 –
0xFFFF
0 = Normal
1 = Error
Bit 00 = Summary Bit (On if any other bit is on)
Bit 01 = Logical Configuration Error
Bit 02 = Demand System Configuration Error
Bit 03 = Energy System Configuration Error
Bit 04 = Reserved
Bit 05 = Metering Configuration Error
3257
Wiring Error Detection
1
— Binary
0x0000 –
0xFFFF
0 = Normal
1 = Error
Bit 00 = Summary Bit (On if any other bit is on)
Bit 01 = Wiring Check Aborted
Bit 02 = System type setup error
Bit 03 = Frequency out of range
Bit 04 = No voltage
Bit 05 = Voltage imbalance
Bit 06 = Not enough load to check connections
Bit 07 = Check meter configured for direct
connect
Bit 08 = All CT reverse polarity
Bit 09 = Reserved
Bit 10 = Reserved
Bit 11 = Reserved
Bit 12 = Reserved
Bit 13 = Reserved
Bit 14 = Phase rotation not as expected
Bit 15 = Negative kW is usually abnormal
Table A–3: Abbreviated Register List
Reg Name Scale Units Range Notes