© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
PMCM-9340D-0208 ACCESS 9340 and 9360 Meters
2/2008 Appendix A—Meter Register List
EN–147
Metering Configuration and Status — Harmonics
3240
Harmonic Quantity
Selection
— 1.0 0 – 3
0 = Disabled
1 = Harmonic magnitudes only (default)
2 = Harmonic magnitudes and angles
3241
Voltage Harmonic
Magnitude Format
— 1.0 0 - 2
0 = % of Fundamental (default)
1 = % of RMS
2 = RMS
3242
Current Harmonic
Magnitude Format
— 1.0 0 - 2
0 = % of Fundamental (default)
1 = % of RMS
2 = RMS
3243
Harmonic Refresh
Interval
— Seconds 10 – 60 Default = 30
3244
Time Remaining Until
Harmonic Refresh
— Seconds 10 – 60
The user may write to this register to stretch
the hold time.
3245
Harmonic Channel
Map
— Binary
0x0000 –
0x7FFF
Bitmap indicating active Harmonic Channels
0 = Inactive
1 = Active
Bit 00 = Vab
Bit 01 = Vbc
Bit 02 = Vca
Bit 03 = Van
Bit 04 = Vbn
Bit 05 = Vcn
Bit 06 = Reserved (Neutral to Ref)
Bit 07 = Ia
Bit 08 = Ib
Bit 09 = Ic
Bit 10 = In
Bit 11-15 = Reserved
3246
Harmonic Report
Status
— 1.0 0 – 1
0 = Processing (default)
1 = Holding
3248
Display 1 second
Metering Floating Point
Values
— — 0 –1
0 = Disabled (default)
1 = Enabled
Values begin at register 11700
Table A–3: Abbreviated Register List
Reg Name Scale Units Range Notes