ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Appendix A—Meter Register List 2/2008
EN–146
3227
Operating Mode
Parameters
Binary
0x0000 –
0x0FFF
Default = 0
Bit 00 = Reserved
Bit 01 = Reactive Energy & Demand
Accumulation
0 = Fund. Only; 1 = Harmonics Included
Bit 02 = PF Sign Convention
0 = IEEE Convention
1 = IEC Convention
Bit 03 = Reserved
Bit 04 = Reserved
Bit 05 = Reserved
Bit 06 = Conditional Energy Accumulation
Control
0 = Inputs; 1 = Command
Bit 07 = Reserved
Bit 08 = Display Setup
0 = Enabled
1 = Disabled
Bit 09 = Normal Phase Rotation
0 = ABC
1 = CBA
Bit 10 = Total Harmonic Distortion Calculation
0 = THD (% Fundamental)
1 = thd (% Total RMS)
Bit 11 = Reserved
3228
Phase Rotation
Direction
1.0 0 – 1
0 = ABC
1 = CBA
3229
Incremental Energy
Interval
Minutes 0 – 1440
Default = 60
0 = Continuous Accumulation
3230
Incremental Energy
Interval Start Time
Minutes 0 – 1440
Minutes from midnight
Default = 0
3231
Incremental Energy
Interval End Time
Minutes 0 – 1440
Minutes from midnight
Default = 1440
3232
Energy Accumulation
Mode
1.0 0 – 1
0 = Absolute (default)
1 = Signed
3233
Peak Current Demand
Over Last Year
(currently not
calculated)
Amps 0 – 32,767
Entered by the user for use in calculation of
Total Demand Distortion.
0 = Calculation not performed (default)
Table A3: Abbreviated Register List