© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
PMCM-9340D-0208 ACCESS 9340 and 9360 Meters
2/2008 Appendix A—Meter Register List
EN–145
Metering Configuration and Status
Metering Configuration and Status — Basic
3200 Metering System Type — 1.0 30, 31, 40, 42
30 = 3PH3W2CT
31 = 3PH3W3CT
40 = 3PH4W3CT (default)
42 = 3PH4W3CT2PT
3201
CT Ratio, 3-Phase
Primary
— 1.0 1 – 32,767 Default = 5
3202
CT Ratio, 3-Phase
Secondary
— 1.0 1, 5 Default = 5
3205
PT Ratio, 3-Phase
Primary
— 1.0 1 – 32,767 Default = 120
3206
PT Ratio, 3-Phase
Primary Scale Factor
— 1.0 -1 – 2
Default = 0
-1 = Direct Connect
3207
PT Ratio, 3-Phase
Secondary
— 1.0
100, 110, 115,
120
Default = 120
3208
Nominal System
Frequency
— Hz 50, 60, 400 Default = 60
3209
Scale A – 3 Phase
Amps
— 1.0 -2 – 1
Power of 10
Default = 0
3210
Scale B – Neutral
Amps
— 1.0 -2 – 1
Power of 10
Default = 0
3212
Scale D – 3 Phase
Volts
— 1.0 -1 – 2
Power of 10
Default = 0
3213 Scale E – Neutral Volts — 1.0 -2 – 2
Power of 10
Default = -1
3214 Scale F – Power — 1.0 -3 – 3
Power of 10
Default = 0
Table A–3: Abbreviated Register List
Reg Name Scale Units Range Notes