ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Appendix A—Meter Register List 2/2008
EN–144
Current/Voltage Configuration
3138
CT Ratio, Phase A
Correction Factor
0.00001 -20,000 – 20,000 Default = 0
3139
CT Ratio, Phase B
Correction Factor
0.00001 -20,000 – 20,000 Default = 0
3140
CT Ratio, Phase C
Correction Factor
0.00001 -20,000 – 20,000 Default = 0
3142
PT Ratio, Phase A
Correction Factor
0.00001 -20,000 – 20,000 Default = 0
3143
PT Ratio, Phase B
Correction Factor
0.00001 -20,000 – 20,000 Default = 0
3144
PT Ratio, Phase C
Correction Factor
0.00001 -20,000 – 20,000 Default = 0
3150
Field Calibration
Date/Time
Table A1
on page 121
Table A1
on page 121
3154
Phase A Current
Field Calibration
Coefficient
0.00001 -20,000 – 20,000 Default = 0
3155
Phase B Current
Field Calibration
Coefficient
0.00001 -20,000 – 20,000 Default = 0
3156
Phase C Current
Field Calibration
Coefficient
0.00001 -20,000 – 20,000 Default = 0
3158
Phase A Voltage
Field Calibration
Coefficient
0.00001 -20,000 – 20,000 Default = 0
3159
Phase B Voltage
Field Calibration
Coefficient
0.00001 -20,000 – 20,000 Default = 0
3160
Phase C Voltage
Field Calibration
Coefficient
0.00001 -20,000 – 20,000
Default = 0
3161
Neutral-Ground
Voltage
Field Calibration
Coefficient
0.00001 -20,000 – 20,000 Default = 0
3170
CT Phase Shift
Correction @ 1 amp
-1,000 – 1,000
Phase Shift Correction in the range of –10º to
+10º. A negative shifts in the lag direction.
Default = 0
3171
CT Phase Shift
Correction @ 5 amps
-1,000 – 1,000
Phase Shift Correction in the range of –10º to
+10º. A negative shifts in the lag direction.
Default = 0
Table A3: Abbreviated Register List
Reg Name Scale Units Range Notes