© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
PMCM-9340D-0208 ACCESS 9340 and 9360 Meters
2/2008 Appendix A—Meter Register List
EN–143
3051 Self Test Results
0x0000 –
0xFFFF
0 = Normal; 1 = Error
Bit 00 = tbd Aux I/O failure
Bit 01 = tbd Option Slot A module failure
Bit 02 = tbd Option Slot B module failure
Bit 03 =
Bit 04 =
Bit 05 =
Bit 06 =
Bit 07 =
Bit 08 = OS Create failure
Bit 09 = OS Queue overrun failure
Bit 10 =
Bit 11 =
Bit 12 =
Bit 13 = Systems shut down due to continuous
reset
Bit 14 = Unit in Download, Condition A
Bit 15 = Unit in Download, Condition B
3052 Configuration Modified
0x0000 –
0xFFFF
Used by sub-systems to indicate that a value
used within that system has been internally
modified
0 = No modifications; 1 = Modifications
Bit 00 = Summary bit
Bit 01 = Metering System
Bit 02 = Communications System
Bit 03 = Alarm System
Bit 04 = File System
Bit 05 = Auxiliary I/O System
Bit 06 = Display System
3093 Present Month Months 1 – 12
3094 Present Day Days 1 – 31
3095 Present Year Years 2,000 – 2,043
3096 Present Hour Hours 0 – 23
3097 Present Minute Minutes 0 – 59
3098 Present Second Seconds 0 – 59
3099 Day of Week 1.0 1 – 7 Sunday = 1
Table A3: Abbreviated Register List
Reg Name Scale Units Range Notes