© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Appendix A—Meter Register List 2/2008
EN–154
4005
Discrete Output Status
Standard Discrete
Output
— — 0x0000 – 0x0001
0 = Off
1= On
Bit 00 = Standard discrete output, I/O
Point 1
Remaining bits unused
4006
Discrete Output Status
Position A
— — 0x0000 – 0xFFFF
0 = Off
1 = On
Bit 00 = On/Off Status of I/O Point 3
Bit 01 = On/Off Status of I/O Point 4
Bit 02 = On/Off Status of I/O Point 5
Bit 03 = On/Off Status of I/O Point 6
Bit 04 = On/Off Status of I/O Point 7
Bit 05 = On/Off Status of I/O Point 8
Bit 06 = On/Off Status of I/O Point 9
Bit 07 = On/Off Status of I/O Point 10
Remaining bits unused
4007
Discrete Output Status
Position B
— — 0x0000 – 0xFFFF
0 = Off
1 = On
Bit 00 = On/Off Status of I/O Point 11
Bit 01 = On/Off Status of I/O Point 12
Bit 02 = On/Off Status of I/O Point 13
Bit 03 = On/Off Status of I/O Point 14
Bit 04 = On/Off Status of I/O Point 15
Bit 05 = On/Off Status of I/O Point 16
Bit 06 = On/Off Status of I/O Point 17
Bit 07 = On/Off Status of I/O Point 18
Remaining bits unused
4008 Reserved — — — Reserved for future development
4010
IO System Diagnostic
Summary
— — 0x0000 – 0x007F
0 = OK
1 = Error
Bit 00 = Summary bit
Bit 01 = I/O Error – Standard
Bit 02 = I/O Error – I/O Position A
Bit 03 = I/O Error – I/O Position B
Remaining bits unused
Table A–4: Registers for Inputs and Outputs
Reg Name Scale Units Range Notes