© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
PMCM-9340D-0208 ACCESS 9340 and 9360 Meters
2/2008 Appendix A—Meter Register List
EN–159
4840 Reserved — — — Reserved for future development
Discrete Input Template
Base IO Point Type — — 100 – 199
• First digit (1) indicates point is discrete input
• Second digit indicates module type
0 = Generic discrete input
• Third digit indicates input type
1 = Unused
2 = AC/DC
Base +1 IO Point Label — — ASCII 16 Characters
Base +9
Discrete Input
Operating Mode
— — 0 – 3
0 = Normal (default)
1 = Demand Interval Sync Pulse
2 = N/A
3 = Conditional Energy Control
4 = Input Metering, used only with external
option modules
Only one Time Sync input and one Conditional
Energy Control are allowed. If the user attempts
to configure more than one of each of these
modes, the lowest I/O Point Number takes
precedence. The modes of the other points will
be set to default.
Base +10
Demand Interval Sync
System Assignments
— — 0x0000 – 0x001F
Bitmap indicating Demand System(s) to which
input is assigned. (Default = 0)
Bit 00 = Power Demand
Bit 01 = Current Demand
Bit 02 = NA
Bit 03 = Input Metering Demand
Bit 04 = Generic Demand 1
Only one Demand Sync Pulse is allowed per
Demand System. If the user attempts to
configure more than one input for each system,
the lowest I/O Point Number takes precedence.
The corresponding bits of the other points are
set to 0.
Base +11 Reserved — — — Reserved for future development
Base +14
Metering Pulse
Channel Assignments
— — 0x0000 – 0x001F
Up to 5 channels are supported
Default = 0
Bit 00 = Channel 1
Bit 01 = Channel 2
Bit 02 = Channel 3
Bit 03 = Channel 4
Bit 04 = Channel 5
Bit 05 – 15 Unused
Table A–4: Registers for Inputs and Outputs
Reg Name Scale Units Range Notes