© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Appendix A—Meter Register List 2/2008
EN–160
Base +15
Metering Pulse Weight
Demand
— 1.0 1– 32,767
Pulse weight associated with the change of
state of the input. Used for demand metering.
(Default = 1)
Base +16
Metering Pulse Scale
Factor Demand
— 1.0 -3 – 3
Pulse weight scale factor (power of 10) to apply
to metering pulse weight. Used for demand
metering. (Default = 0)
Base +17
Metering Pulse Weight
Consumption
— 1.0 1– 32,767
Pulse weight associated with the change of
state of the input. Used for consumption
metering. (Default = 1)
Base +18
Metering Pulse Scale
Factor
Consumption
— 1.0 -3 – 3
Pulse weight scale factor (power of 10) to apply
to metering pulse weight. Used for consumption
metering. (Default = 0)
Base +19
Consumption Units
Code
—
See
Template
0 - 100
Defines the units associated with the
Consumption Pulse Weight/Scale (Default = 0)
Base +20 Reserved — — — Reserved for future development
Base +22
IO Point Diagnostic
Bitmap
— — 0x0000 – 0xFFFF
0 = OK, 1 = Error
Bit 00 = I/O Point diagnostic summary
Bit 01 = Configuration invalid – default value
used
Base +23 Reserved — — — Reserved for future development
Base +25
Discrete Input On/Off
Status
— — 0 – 1
0 = Off
1 = On
Base +26 Count — — 0 – 99,999,999
Number of times input has transitioned from Off
to On
Base +28 On Time — Seconds 0 – 99,999,999 Duration that discrete input has been On
Discrete Output Template
Base IO Point Type — — 200 – 299
• First digit (2) indicates point is discrete
output
• Second digit indicates module type
0 = Generic discrete output
• Third digit indicates output type
1 = solid state relay
2 = electromechanical relay
Base +1 IO Point Label — — ASCII 16 Characters
Table A–4: Registers for Inputs and Outputs
Reg Name Scale Units Range Notes