PMCM-9340D-0208 ACCESS 9340 and 9360 Meters
2/2008 Appendix A—Meter Register List
EN–161
Base +9
Discrete Output
Operating Mode
0 – 11
0 = Normal (default)
1 = Latched
2 = Timed
11 = End of power demand interval
The following modes are only supported by the
standard output (KY). No support is provided for
the I/O option modules:
3 = Absolute kWh pulse
4 = Absolute kVARh pulse
5 = kVAh pulse
6 = kWh In pulse
7 = kVArh In pulse
8 = kWh out pulse
9 = kVARh out pulse
10 = Register-based pulse (future)
Base +10
On Time For Timed
Mode
Seconds 1 – 32,767
The time for the output to remain energized
when the output is in timed mode or end of
power demand interval. (Default = 1)
Base +11 Pulse Weight
kWh / Pulse
kVArH /
Pulse
kVAH /
Pulse
in 100ths
1 – 32,767
Specifies the kWh, kVARh and kVAh per pulse
for output when in these modes. (Default = 1)
Base +12
Internal/External
Control
0 – 1
0 = Internal Control
1 = External Control (default)
Base +13
Normal/Override
Control
0 – 1
0 = Normal Control (default)
1 = Override Control
Base +14 Reference Register Reserved for future development
Base +15 Reserved Reserved for future development
Base +16 Reserved Reserved for future development
Base +17 Reserved Reserved for future development
Base +18 Reserved Reserved for future development
Base +19 Reserved Reserved for future development
Base +20 Reserved Reserved for future development
Base +21
State of Discrete
Output at Reset
0 – 1
Indicates On/Off state of the discrete output
when meter reset/shutdown occurs
Table A4: Registers for Inputs and Outputs