ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Appendix A—Meter Register List 2/2008
EN–180
Alarms — Template 1
Base Unique Identifier
0 –
0xFFFFFFFF
Bits 00 – 07 = Level (0 – 9)
Bits 08 – 15 = Alarm Type
Bits 16 – 31 = Test Register
For Disturbance alarms Test Register is:
1 = Vab
2 = Vbc
3 = Vca
4 = Van
5 = Vbn
6 = Vcn
7 = Vng
8 = Ia
9 = Ib
10 = Ic
11 = In
For Unary Alarms, Test Register is:
1 = End of Incremental Energy Interval
2 = End of Power Demand Interval
3 = End of 1s Meter Update Cycle
4 = Reserved
5 = Power up/ Reset
Base +2 Enable/Disable, Priority
MSB: 0 – FF
LSB: 0 – 3
MSB:
0x00 = Disabled (Default)
0xFF = Enabled
LSB: Specifies the priority level 0 – 3
Base +3 Label ASCII 16 Characters
Base +11 Pickup Value A-F Units/Scale 0 – 32,767 Does not apply to digital or unary alarms
Base +12 Pickup Delay 1s Cycle
0 – 32,767
0 – 999
0 – 999
Standard Speed Alarms
Disturbance Alarms
Does not apply to digital or unary alarms.
Base +13 Dropout Value
A-F
Units/Scale 0 – 32,767 Does not apply to digital or unary alarms.
Base +14 Dropout Delay 1s Cycle
0 – 32,767
0 – 999
0 – 999
Standard Speed Alarms
Disturbance Alarms
Does not apply to digital or unary alarms.
Base +15 Reserved Reserved for future development
Base +16 Datalog Specifier
0 –
0xFFFFFFFF
Bit 00 = Datalog #1
Bit 01 = Datalog #2 (PM850, 9360DC)
Bit 02 = Datalog #3 (PM850, 9360DC)
Table A6: Registers for Alarm Position Counters
Reg Name Scale Units Range Notes