© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
PMCM-9340D-0208 ACCESS 9340 and 9360 Meters
2/2008 Appendix A—Meter Register List
EN–181
Alarms — Template 2
Base Unique Identifier — —
0 –
0xFFFFFFFF
Bits 00 – 07 = Level (0 – 9)
Bits 08 – 15 = Alarm Type
Bits 16 – 31 = Test Register
Base +2 Enable/Disable, Priority — —
MSB: 0 – FF
LSB: 0 – 3
MSB: 0x00 = Disable; 0xFF = Enable
LSB: Specifies the priority level 0 – 3
Base +3 Label — — ASCII 16 Characters
Base +11 Alarm test list — — 0 – 74 Alarm test list (position # in the normal alarm list)
Table A–6: Registers for Alarm Position Counters
Reg Name Scale Units Range Notes
Table A–7: Abbreviated Floating-Point Register List
Reg Name Units Notes
1s Metering – Current
11700 Current, Phase A Amps RMS
11702 Current, Phase B Amps RMS
11704 Current, Phase C Amps RMS
11706 Current, Neutral Amps
RMS
4-wire system only
11708 Current, Ground Amps
RMS
4-wire system only
11710 Current, 3-Phase Average Amps Calculated mean of Phases A, B & C
1s Metering – Voltage
11712 Voltage, A-B Volts RMS Voltage measured between A & B
11714 Voltage, B-C Volts RMS Voltage measured between B & C
11716 Voltage, C-A Volts RMS Voltage measured between C & A
11718 Voltage, L-L Average Volts RMS 3 Phase Average L-L Voltage
11720 Voltage, A-N Volts
RMS Voltage measured between A & N
4-wire system only
11722 Voltage, B-N Volts
RMS Voltage measured between B & N
4-wire system only
11724 Voltage, C-N Volts
RMS Voltage measured between C & N
4-wire system only
11726 Voltage, N-G Volts
RMS Voltage measured between N & G
4-wire system with 4 element metering only
11728 Voltage, L-N Average Volts RMS 3-Phase Average L-N Voltage
1s Metering – Power
11730 Real Power, Phase A W
Real Power (PA)
4-wire system only
11732 Real Power, Phase B W
Real Power (PB)
4-wire system only
11734 Real Power, Phase C W
Real Power (PC)
4-wire system only