ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Appendix A—Meter Register List 2/2008
EN–182
11736 Real Power, Total W
4-wire system = PA+PB+PC
3-wire system = 3-Phase real power
11738 Reactive Power, Phase A VAr
Reactive Power (QA)
4-wire system only
11740 Reactive Power, Phase B VAr
Reactive Power (QB)
4-wire system only
11742 Reactive Power, Phase C VAr
Reactive Power (QC)
4-wire system only
11744 Reactive Power, Total VAr
4-wire system = QA+QB+QC
3 wire system = 3-Phase reactive power
11746 Apparent Power, Phase A VA
Apparent Power (SA)
4-wire system only
11748 Apparent Power, Phase B VA
Apparent Power (SB)
4-wire system only
11750 Apparent Power, Phase C VA
Apparent Power (SC)
4-wire system only
11752 Apparent Power, Total VA
4-wire system = SA+SB+SC
3-wire system = 3-Phase apparent power
1s Metering – Power Factor
11754 True Power Factor, Phase A
Derived using the complete harmonic content of real
and apparent power.
4-wire system only
11756 True Power Factor, Phase B
Derived using the complete harmonic content of real
and apparent power.
4-wire system only
11758 True Power Factor, Phase C
Derived using the complete harmonic content of real
and apparent power.
4-wire system only
11760 True Power Factor, Total
Derived using the complete harmonic content of real
and apparent power
1s Metering – Frequency
11762 Frequency Hz
Frequency of circuits being monitored. If the
frequency is out of range, the register will be -32,768.
Energy
11800 Energy, Real In WH 3-Phase total real energy into the load
11802 Energy, Reactive In VArH 3-Phase total reactive energy into the load
11804 Energy, Real Out WH 3-Phase total real energy out of the load
11806 Energy, Reactive Out VArH 3-Phase total reactive energy out of the load
11808
Energy, Real Total
(signed/absolute)
WH Total Real Energy In, Out or In + Out
11810
Energy, Reactive Total
(signed/absolute)
VArH Total Reactive Energy In, Out or In + Out
11812 Energy, Apparent VAH 3-Phase total apparent energy
11814 Energy, Conditional Real In WH
3-Phase total accumulated conditional real energy into
the load
11816
Energy, Conditional Reactive
In
VArH
3-Phase total accumulated conditional reactive energy
into the load
Table A–7: Abbreviated Floating-Point Register List
Reg Name Units Notes