ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Appendix C—EN50160 Evaluation 2/2008
EN–232
Table C5: Portal Register Descriptions
Portal Description Size Data
53432 –
53434
Summary of
Meter Data
Evaluations
by Item
33
Register number of Metered Quantity (can be used to confirm
data item being reported)
Register value (present metered value)
Average value (at end of last completed averaging time period)
Minimum value during the last completed averaging time period
Maximum value during the last completed averaging time period
Minimum value during this interval
Maximum value during this interval
Minimum value during the last interval
Maximum value during the last interval
Percent in Evaluation Range 1 this interval
Percent in Evaluation Range 2 this interval (when applicable)
Percent in Evaluation Range 1 last interval
Percent in Evaluation Range 2 last interval (when applicable)
Count of average values in Evaluation Range 1 (MOD10L2)
Count of average values in Evaluation Range 2 (MOD10L2)
Count of total valid averages for Evaluation of Range 1
(MOD10L2)
Count of total valid averages for Evaluation of Range 2
(MOD10L2)
Date/Time Last Excursion Range 1 (4-register format)
Date/Time Last Excursion Range 2 (4-register format)
Date/Time Last Reset (4-register format)
53435 –
53437
Summary of
Rapid
Voltage
Changes by
Phase
12
Count of rapid voltage increases this week
Count of rapid voltage decreases this week
Count of rapid voltage increases last week
Count of rapid voltage decreases last week
Date/Time last rapid voltage change (4-register format)
Date/Time last reset (4-register format)
53438 –
53440
Summary of
Voltage Dips
by Phase
This Week
104
Count of dips by magnitude & duration this week (96 values) [See
“Detection and Classification of Supply Voltage Dips” on page
225.]
Date/Time last voltage dip (4-register format)
Date/Time last reset (4-register format)