PMCM-9340D-0208 ACCESS 9340 and 9360 Meters
2/2008 Appendix C—EN50160 Evaluation
EN–233
53441 –
53443
Summary of
Voltage Dips
by Phase
Last Week
104
Count of dips by magnitude & duration last week (96 values) [See
“Detection and Classification of Supply Voltage Dips” on page
225.
Date/Time last voltage dip (4-register format)
Date/Time last reset (4-register format)
53444 –
53447
Summary of
Supply
Voltage
Interruptions
3-Phase and
by Phase
34
Flag indicating interruption is active
Elapsed seconds for interruption in progress
Count of short interruptions this year
Count of long interruption this year
Count of short interruptions last year
Count of long interruptions last year
Count of interruptions by duration this year (10 values) [See
“Detection of Interruptions of the Supply Voltage” on page 226.]
Count of interruptions by duration last year (10 values) [See
“Detection of Interruptions of the Supply Voltage” on page 226.]
Date/Time of last interruption (4-register format)
Date/Time of last reset (4-register format)
53448 –
53449
Temporary
Power
Frequency
Overvoltage
s by Phase
This Week
104
Count of overvoltages by magnitude & duration this week (96
values) [See “Detecting and Classifying Temporary Power
Frequency Overvoltages” on page 226.]
Date/Time last overvoltage (4-register format)
Date/Time last reset (4-register format)
53450 –
53452
Temporary
Power
Frequency
Overvoltage
s by Phase
Last Week
104
Count of overvoltages by magnitude & duration last week (96
values) [See “Detecting and Classifying Temporary Power
Frequency Overvoltages” on page 226.]
Date/Time last overvoltage (4-register format)
Date/Time last reset (4-register format)
Table C–5: Portal Register Descriptions
Portal Description Size Data