© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Appendix C—EN50160 Evaluation 2/2008
EN–234
53312
Evaluation
Summary
Bitmap
18
Register 1 – Bitmap of active
evaluations (same as register
3910)
Bit set when evaluation is active
Bit 00 – Summary bit – at least
one EN50160 evaluation is
active
Bit 01 – Frequency
Bit 02 – Supply voltage
variations
Bit 03 – Magnitude of rapid
voltage changes
Bit 04 – Not used
Bit 05 – Supply voltage dips
Bit 06 – Short interruptions of
the supply voltage
Bit 07 – Long interruptions of
the supply voltage
Bit 08 – Temporary power
frequency overvoltages
Bit 09 – Not used
Bit 10 – Supply voltage
unbalance
Bit 11 – Harmonic voltage
Bit 12 – THD
Bit 13 – Not used
Bit 14 – Not used
Bit 15 – Not used
Register 2 – Bitmap of
evaluation status summary
(same as register 3911)
Bit set when evaluation fails
Bit 00 – Summary bit – at least
one EN50160 evaluation has
failed
Bit 01 – Frequency
Bit 02 – Supply voltage
variations
Bit 03 – Magnitude of rapid
voltage changes
Bit 04 – Not used
Bit 05 – Supply voltage dips
Bit 06 – Short interruptions of
the supply voltage
Bit 07 – Long interruptions of
the supply voltage
Bit 08 – Temporary power
frequency overvoltages
Bit 09 – Not used
Bit 10 – Supply voltage
unbalance
Bit 11 – Harmonic voltage
Bit 12 – THD
Bit 13 – Not used
Bit 14 – Not used
Bit 15 – Not used
Table C–5: Portal Register Descriptions
Portal Description Size Data