E3M111 Line module ”SynoLOOP”
38
Siemens Building Technologies 007831_a_en_--.doc
Fire & Security Products 03.2004
10.4 Important components
Fuses
F1 7 1A/T* Module supply 24V
F1 8 1A/T* Module supply 5V
* Fuse with high breaking capacity
(sand-filled)
Fuses
F1...F16 1A/F Lines 1..4
SMD fuses (can only be changed at factory)
Plug-in terminals "K1":
Supply to "I-Bus" modules
Flat cable header "ST1" (26-pin):
I-Bus
Programming switch "S3":
"I-Bus address" setting
(see chapter Programming switch)
Connector 'ST10':
unused
Fuses
F19/F20 1A/F
Supply voltage for DC modules
SMD fuses (can only be
changed at factory)
Service LED "H1":
pulsating = Communication with detection line(s) ok
continuous = Module probably defective
not active = no line connected, or not programmed
E3M111
F1
F16
F20
F19
H1
S3
ST1
ST10
F18
F17
K1
ON
1
1
4
µ
P
ASIC
I-Bus
10.5 Programming switch ”S3”
To set I-Bus address. Each element (module) connected to the I-Bus must have an
individual address (number). This is set on programming switch ”S3”. Maximum 16
I-Bus devices.
Function / I-Bus address Programming switch S3
No. S3-1 S3-2 S3-3 S3-4 S3-5 S3-6
0 Module out of commission (unused) off off off off off off
1 I-Bus user number 1 on off off off off off
2 2 off on off off off off
3 3 on on off off off off
4 4 off off on off off off
5 5 on off on off off off
6 6 off on on off off off
7 7 on on on off off off
8 8 off off off on off off
9 9 on off off on off off
10 10 off on off on off off
11 11 on on off on off off
12 12 off off on on off off
13 13 on off on on off off
14 14 off on on on off off
15 15 on on on on off off
16 16 off off off off on off
”S3-1...6” are set to ”off” at the factory