EasyManua.ls Logo

Siemens FC700A - Programming Switch S5 and Connections

Siemens FC700A
108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
B3Q700 Control terminal to FC/FT
79
Siemens Building Technologies 007831_a_en_--.doc
Fire & Security Products 03.2004
20.7 Programming switch ’S5’
’S5-1...4’ are set to ”off” at the factory.
on Maintenance mode: Blocks all control outputs S5-1
off Normal operation
off Event memory, normal mode S5-2
on Event memory, freeze current contents
S5-3 off Unused
off Flash programming disabled S5-4
*
on Flash programming enabled (function for production und service engineer only)
*) Carry out a CPU reset (switch ’S1’) after each switch over of ’S5-4’.
20.8 Connections
Supply I-Bus modules
3
2
1
+
+
Plug-in terminals "orange"
K1
24V
5V
to the I-Bus modules
with application 'FC' -> as input to E3C011
with application ‘FT’ -> is only used, if the LON
module E3I040 is connected
1
2
1
Plug-in terminals "orange"
K4
Operat.enabled
C
external operation
enabled
1
2
3
4
1
Plug-in terminals "grey"
K5
C-Bus
B1
A1
B2
A2
1
2
3
1
Plug-in terminals "orange"
K6
Emergency
operation
C
F3
Fire alarm
F4
Switch off horn
1
2
3
4
5
6
+
-
+
-
1
Plug-in terminals "orange"
K7
F2
F1
additional B3Q700
see chapter
Wiring principle (C-Bus)
1)
C-Bus must be wired as a loop line if more then one C-Bus participants are connected
always
2)
Configuration as in-/or output see jumpers X31, X32, X33, X34, Y31, Y32, Y33, Y34 on table in chapter important components
4
blue
blue
green
red
External key switch
GND
-
-
- Cabling C-bus
max. 1000m per loop with ø 0,6mm wire
max. 1400m per loop with ø 0,8mm wire
(always including return line)
-for cable type (impedance adaption) see
chapter Wiring principle (C-Bus)
Supply 1
Supply 2
1
2
3
4
1
Plug-in terminals "orange"
K2
C
B3Q700
2)
Inputs TROUBLE
power supply
(default = not active)
Emerg. power
Power supply
Battery
Local power supply
(internal only)
1)
3
4
1
2
B2
A2
B1
A1
K5
B3Q700
2
3
1
K6
2
3
4
5
6
1
+
-
+
-
K7

Table of Contents

Other manuals for Siemens FC700A

Related product manuals