E3L030 Control module VdS
62
Siemens Building Technologies 007831_a_en_--.doc
Fire & Security Products 03.2004
15.5 Programming switch ”S3”
To set I-Bus address. Each element (module) connected to the I-Bus must have an
individual address (number). This is set on programming switch ”S3”. Maximum 16
I-Bus devices.
Function / I-Bus address Programming switch S3
No. S3-1 S3-2 S3-3 S3-4 S3-5 S3-6
0 Module out of commission (unused) 1) off off off off off off
1 I-Bus user number 1 on off off off off off
2 2 off on off off off off
3 3 on on off off off off
4 4 off off on off off off
5 5 on off on off off off
6 6 off on on off off off
7 7 on on on off off off
8 8 off off off on off off
9 9 on off off on off off
10 10 off on off on off off
11 11 on on off on off off
12 12 off off on on off off
13 13 on off on on off off
14 14 off on on on off off
15 15 on on on on off off
16 16 off off off off on off
”S3-1...6” is set to ”off” at the factory
1) E3L030 functions in ”emergency operation” with I-Bus address 0
15.6 Special functions
Emergency operation
An alarm which occurs during system malfunction (emergency operation) can still
be handled via FBF and ÜE and FSD can also still be activated.
Function overview during ”emergency operation”
Function Emergency
operation E3L030
Emergency
operation CPU
FBF
Indicator ”ÜE activated” ● ●
Indicator ”LEDs 5, 6, 7, T5 operational” - ●
Function ”Silence audible signal” ● ●
ÜE
Function ”Activate ÜE” ● ●
FSD
Function ”Activate FSD unlocking” ● ●
SST (Extinguishing standard interface) - -
TK (Door switch control unit) - ●