Parameterization
9.3 Parameters
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
121
9.3.1
P01 - Settings
P01
Settings
Designation on ATC
display
Description
Unit
Default
Range
P01.01 Language Sets the language
This parameter is used for setting the lan-
guage of the user interface.
English English
Italiano
Francais
Espanol
Deutsch
P01.02 Clock setting PWR
ON
Setting of the real-time clock when switching on
the power supply
This parameter determines whether the real-
time clock is to be reset or not after each
startup.
OFF OFF-ON
P01.03 Op. mode at power
on
Operating mode after switching on
This parameter determines which mode the
ATC6300 enters after switching on. It can either
be always switched on in the operating mode
OFF, or in the last operating mode used before
the device was switched off.
Previous OFF mode
Previous
P01.04 Display contrast Display contrast
This can be used to adjust the contrast of the
LCD display.
% 50 0-100
P01.05 High backlight level High backlight level
This parameter sets the bright LCD backlight-
ing.
% 100 0-100
P01.06 backlight delay Low backlight level
This parameter sets the low LCD backlighting.
% 25 0-50
P01.07 Load no backlight
delay
Delay low LCD backlighting
This allows you to set a delay time, after
which the ATC6300 switches to low backlight-
ing.
s 180 5-600
P01.08 ret. page return Default page return
This parameter controls whether the device
switches to a default page defined under
P01.09 if no key is pressed within a specific
time. If this parameter is set to OFF, the
ATC6300 always remains on the last page to
be opened.
s 300 OFF / 10-600
P01.09 Default page Selection of the default page
This parameter is used to select a new default
page from the existing display pages of the
ATC6300. In connection with P01.08, a switch
is made to this page after a certain time.
VL-L (List with dis-
play pages)
P01.10 Transfer Switch ID Plant identifier
You can enter any alphanumeric description
of the plant here.
SIEMEN
S
ATC630
0
String 20 chr.