Parameterization
9.3 Parameters
3KC ATC6300 transfer control device
124 Manual, 03/2018, L1V30535632002A-01
9.3.4
P04 - Battery
Note
Use of DC power supply
The following parameters are necess
ary only if you are using a DC power supply (see
chapter
Connecting the power supply (Page 70)).
P04
Battery
Designation on ATC
display
Description
Unit
Default
Range
P04.01 Battery voltage Nominal voltage of the DC supply
This parameter defines the voltage of the
additional DC supply of the ATC6300.
Note: If this parameter is set to OFF, all alarms
regarding the DC supply, as well as the indica-
tor for the battery voltage, are disabled.
V AUTO AUTO
12
24
OFF
P04.02 Max voltage limit Maximum voltage limit of the DC supply
This defines the upper limit threshold for the
battery voltage.
% 130 110 - 140
P04.03 Min voltage limit Minimum voltage limit of the DC supply
This defines the lower limit threshold for the
battery voltage.
% 75 60 - 130
P04.04 Min / Max volt. delay
Minimum / maximum voltage delay of the DC
supply
This parameter defines the delay for the min-
imum / maximum DC supply voltage. If the
voltage exceeds the upper or lower limits from
P04.02 and P04.03 for the period defined by
this parameter, the corresponding alarms are
triggered.
s 10 0 - 120