Connection
7.1 General connection drawings
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
69
7.1.3
Connection of contactors
Note
Implementation of the power supply
If you do not use an external DC source v
ia inputs 31 and 32, the continuous power supply
of the ATC6300 must be provided by a dual network connection or, for example, by means
of a voltage relay (see chapter
Connection of the power supply (Page 70)).
For the circuit diagram illustrated here, the following parameters are to be set:
Terminal
Parameter code
Setting
P05.07
Contactors
15(INP1)
P10.01.01
Line 1 breaker closed (feedback 1)
16(INP2)
P10.02.01
Line 2 breaker closed (feedback 2)
27(OUT5)
P11.05.01
Close Line 1 contactor/circuit breaker
30(OUT7)
P11.07.01
Close Line 2 contactor/circuit breaker