Operation
8.3 Designation and description of the outputs
3KC ATC6300 transfer control device
112 Manual, 03/2018, L1V30535632002A-01
Table of functions of the digital outputs
The table below lists all functions that can be assigned to the programmable digital outputs
OUTx.
Configurable Free configuration by the user.
Close Line 1 contactor/circuit breaker Command to close the contactor/circuit breaker
Open Line 1 contactor/circuit breaker Command to open the circuit breaker of Line 1
with possible spring load.
Close Line 2 contactor/circuit breaker Command to close contactor/circuit breaker of
Open Line 2 contactor/circuit breaker Command to open the circuit breaker of Line 2
with possible spring load.
Open Line 1 and Line 2 Open both circuit breakers / neutral position of
the transfer switching equipment with motor op-
Min coil Line 1 Controls the undervoltage release by opening
breaker 1 before the spring load cycle.
Min coil Line 2 Controls the undervoltage releases by opening
breaker 2 before the spring load cycle.
Line 1 generator control Control of the Start / Stop remote control of the
Line 2 generator control Control of the Start / Stop remote control of the
ATC ready ATC in automatic mode, without alarms, ready to
Global alarm Output enabled in the presence of any alarm with
the property "Global alarm enabled".
Line 1 status This output is enabled if all conditions for the
connection of the load to Line 1 have been met.
Line 2 status This output is enabled if all conditions for the
connection of the load to Line 2 have been met.
Siren Supplies power to the siren for the acoustic sig-
Operating mode This output is enabled if the ATC is in one of the
operating modes set with parameter P12.03.
Enabled if the ATC is in the OFF mode.
Enabled if the ATC is in the MAN mode.
Enabled if the ATC is in the AUT mode.
Remote variable REM (x) Output controlled by remote variable REMx
Limit threshold LIM (x) Output controlled by the status of the limit thresh-
old LIM(x), (x=1..4); defined by the Index parame-
Dummy (dummy load) This output is enabled if the automatic test is
performed with dummy load.