Connection
7.3 Connection of Siemens SENTRON switching devices
3KC ATC6300 transfer control device
86 Manual, 03/2018, L1V30535632002A-01
Typical operating times of the Siemens SENTRON switching devices in accordance
with IEC 60947-6-1 (IEC only)
The following typical operating times can be achieved with the ATC and Siemens circuit
breakers in accordance with IEC 60947-6-1. Take the operating times for the 3KC3 and
3KC4 remotely operated transfer switching equipment from the corresponding manual or
catalog.
Note
The tables below contain typical operating values. Check t
he operating times of the
respective total installation under real conditions.
Operating times of the 3VA
Contact transfer time,
off-time*
ms 900 900 1100 180 1100
ms 800 800 1000 80 1000
Transfer time I-O-II,
II-O-I (for min para-
meter)*
ms 1700 1700 2100 260 2100
* Comprises the minimum delay time from Line I to Line II of 100 ms (see parameter P05.03) in the OFF position
Contact transfer time,
off-time*
ms 180 1100 180 1800 1800
ms 80 1000 80 1400 1400
Transfer time I-O-II,
II-O-I (for min para-
meter)*
ms 260 2100 260 3200 3200
* Comprises the minimum delay time from Line I to Line II of 100 ms (see parameter P05.03) in the OFF position