Parameterization
9.3 Parameters
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
143
9.3.15
P15 - User alarms
This menu is divided into 4 sections for the definition of the user alarms UA1 ... UA4.
You can find more information in chapter User alarms (Page 50).
P15 User
alarms
(UAn,
n=1…4)
Designation on
ATC display
Description
Default
Range
P15.n.01 Source Alarm source
Defines the digital input or of the internal variable that
generates the user alarm when it is activated.
OFF OFF
INPx
OUTx
LIMx
REMx
P15.n.02 Channel number Channel number (x)
Channel number, with reference to the previous parame-
ter
1 OFF / 1 ... 99
P15.n.03 Description Description
Freely selectable text that is shown in the alarm window.
UAn (Text – 20
chars)
P15.n.04 Breaker opening Opening of the circuit breaker
It is defined which breaker is to be opened when this
alarm occurs.
Example
: The user alarm UA3 must be generated by the
closing of input INP5 and must display the message
"Doors open".
In this case, the menu section 3 must be configured (for
alarm UA3):
P15.3.01 = INPx
P15.3.02 = 5
P15.3.03 = ‘Doors open’
OFF OFF
1
2
1+2