Parameterization
9.3 Parameters
3KC ATC6300 transfer control device
140 Manual, 03/2018, L1V30535632002A-01
This menu is divided into 4 sections for the limit thresholds LIM1 ... 4.
You can find more information on the user limits in chapter User limit threshold LIMx
(Page 57).
P13
User limit
thresholds
(LIMn, n =
1…4)
Designation on
ATC display
P13.n.01 Reference meas-
urement
Reference measurement
- Defines which measurements of the ATC6300
the limit threshold is applied to. For the list of
reference measurements, refer to chapter
User
limit threshold LIMx. (Page 57)
OFF OFF-
(List of meas-
urements) ….
P13.n.02 Reference source Source of reference measurement
– If the reference measurement involves an
electrical measurement, this parameter speci-
fies whether it refers to Line 1 or Line 2.
OFF OFF
Line 1
Line 2
P13.n.03 Channel number No. channel No. (x)
– If the reference measurement is an internal
multi-channel measurement, the channel num-
1 OFF / 1 ... 99
P13.n.04 Function Function
– Defines the mode of operation of the limit
threshold (see chapter
User limit threshold
Max Max
Min
Min + Max
P13.n.05 Upper threshold Upper threshold
– Defines the upper threshold obtained by mul-
tiplying the value of P13.n.06 by the value of
0 -9999 - +9999
P13.n.06 Multiplier Multiplier
x1 /100 – x10k
P13.n.07 Delay Delay
– Upper threshold intervention delay.
s 0 0.0 – 600.0
P13.n.08 Lower threshold Lower threshold
– As above, but relating to the lower threshold.
0 -9999 - +9999
P13.n.09 Multiplier Multiplier
x1 /100 – x10k
P13.n.10 Delay Delay
s 0 0.0 – 600.0