Functions
5.1 Basic functions
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
47
5.1.6.1
Properties of the alarms
Various properties can be assigned to each alarm, including the user alarms (UAx see
chapter User alarms (Page 50)).
Alarms enabled (active)
General enabling of the alarm.
If an alarm has not been enabled, the procedure is as if the alarm did not exist.
Only AUT (Aut)
The alarm can only be triggered if the ATC6300 is in automatic mode.
Retention alarm (Retent)
Remains stored, even after the triggering cause has been removed.
Global alarm (Glb Al)
Activates the output which is assigned to this global alarm function (see chapter Table of
functions of the digital outputs (Page 112))
Lock BRK1 (Lock 1)
On occurrence of the alarm, no further commands are sent to switching device 1.
Lock BRK2 (Lock 2)
On occurrence of the alarm, no further commands are sent to switching device 2.
Siren (Siren)
Activates the output assigned to this function, as configured in the Table of alarms
(Page 49)
Inhibit (Inhib.)
The alarm can be temporarily deactivated by activating a programmable input with the
alarm inhibit function.
No LCD (No LCD)
The alarm is managed normally, but not shown on the display.