Accessories
12.1 Expansion modules
3KC ATC6300 transfer control device
178 Manual, 03/2018, L1V30535632002A-01
5 V DC (supplied through the ATC6300)
Current consumption (max.) 290 mA
Input type Positive or negative (depending on the connec-
tion of the control terminal COM)
Note: All inputs must have the same polarity
Input signal - logical state "0" ≤ 2 V (if COM is connected to -)
≥ 22 V (if COM is connected to +)
Input signal - logical state "1" ≥ 7.6 V (if COM is connected to -)
≤ 12.4 V (if COM is connected to +)
Maximum frequency 2000 Hz (if the input is configured as a counter)
50 Hz (if input is configured as status)
Cable cross-section (min-max)
2
Control terminal COM and auxiliary supply terminals + and -
Auxiliary power supply at + and - 24 V DC (see tolerance graph in chapter Expan-
sion module 4DI (Page 176))
Maximum current at + and - 42 mA (protected against overload and short-
circuit)
: If the maximum current is exceeded, the
protection is enabled and the voltage drops
Cable cross-section (min-max)
2
Cable cross-section (min-max) acc. to UL 508
2
Impulse withstand voltage U
imp
Operating frequency impulse withstand voltage
< 80 % (IEC / EN 60068-2-70)
Maximum degree of pollution