Parameterization
9.3 Parameters
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
139
9.3.12
P12 - Miscellaneous
P12
Miscella-
neous
Designation on
ATC display
Description
Unit
Default
Range
P12.01 Maintenance inter-
val
Maintenance interval hours
Defines in hours the programmed time inter-
val for scheduled maintenance. If this parame-
ter is set to OFF this maintenance interval is
disabled.
h OFF OFF
1 … 99999
P12.02 Maintenance
Counter
Maintenance interval operating cycles
Defines the programmed time interval for
scheduled maintenance in number of operating
cycles. If this parameter is set to OFF this
maintenance interval is disabled.
OFF OFF
1 … 99999
P12.03 Operating mode
out.
Output operating mode
Defines in which operating mode the output
programmed to the function is to be enabled.
For example, if this parameter is set to M-O, the
operating mode output is enabled when the
ATC6300 is in the MAN or OFF mode.
OFF OFF
O
M
M O
A
A-O
A-M
A-M-O