Parameterization
9.3 Parameters
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
139
Designation on
ATC display
P12.01 Maintenance inter-
val
Maintenance interval hours
– Defines in hours the programmed time inter-
val for scheduled maintenance. If this parame-
ter is set to OFF this maintenance interval is
h OFF OFF
1 … 99999
P12.02 Maintenance
Counter
Maintenance interval operating cycles
– Defines the programmed time interval for
scheduled maintenance in number of operating
cycles. If this parameter is set to OFF this
maintenance interval is disabled.
OFF OFF
1 … 99999
P12.03 Operating mode
out.
Output operating mode
– Defines in which operating mode the output
programmed to the function is to be enabled.
For example, if this parameter is set to M-O, the
operating mode output is enabled when the
ATC6300 is in the MAN or OFF mode.
OFF OFF
O
M
M – O
A
A-O
A-M