Parameterization
9.3 Parameters
3KC ATC6300 transfer control device
138 Manual, 03/2018, L1V30535632002A-01
This menu is divided into 15 sections. These refer respectively to the 7 possible digital
outputs OUT1 … OUT7 that can be managed directly by the ATC6300, and a further 8
outputs that can be managed by the ATC6300 via the expansion modules.
P11
Digital ou-
tputs (OUTn,
n = 1…15)
Designation on
ATC display
P11.n.01 Output function Function of the output OUTn
– Selects the function of the selected output (See Table of
outputs in chapter Digital outputs OUTx (Page 110))
- See Table of
outputs
(Page 112)
P11.n.02 Channel number Function index (x)
– Index that is possibly assigned to the function pro-
grammed in the previous parameter.
: If the output function is set to the function Alarms
Axx, and this output is to be enabled when the Alarm A16
occurs, P11.n.02 must be set to the value 16.
1 OFF / 1 … 99
P11.n.03 Output type Normal / reverse output
– Sets the status of the output if the function assigned to it
is inactive: NOR = Output de-energized, REV = output
NOR NOR / REV