MODBUS communication
11.6 Data library
3KC ATC6300 transfer control device
166 Manual, 03/2018, L1V30535632002A-01
11.6.4
Status of the ATC (use with MODBUS function 03 and 04)
Address
Words
Function
Format
2210H
2
Status of the ATC (bit 0 - bit 31)
unsigned integer
The meaning of the 32 bits of the address 2210H can be viewed below:
Bit
Meaning
0
ATC OFF
1
ATC in MAN mode
2
ATC in AUT mode
3
ATC in Test mode
4
Voltage Line 1 OK
5
Voltage Line 2 OK
6
LED Line 1 enabled
7
LED Line 2 enabled
8
LED load on Line 1 enabled
9
LED load on Line 2 enabled
10
Mains breaker closed
11
Generator breaker closed
12
Global alarm
13
AC power supply
14
Start generator 1
15
Start generator 2
16
Line 1 maximum voltage
17 Line 1 minimum voltage
18
Line 1 maximum frequency
19
Line 1 minimum frequency
20
Line 1 phase failure
21
Line 1 phase unbalance
22
Line 2 maximum voltage
23
Line 2 minimum voltage
24
Line 2 maximum frequency
25
Line 2 minimum frequency
26
Line 2 phase failure
27
Line 2 phase unbalance
28
Not used
29
Not used
30
Not used
31
Not used