3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
195
Auxiliary power supply: Terminal 13,14
Supply voltage U
s
100 ... 240 V AC
Operating range 90 ... 264 V AC
Interference strength against voltage dips
- without expansion modules ≤ 50 ms (at 110 V AC)
- with 2 expansion modules ≤ 25 ms (at 110 V AC)
≤ 120 ms (at 220 V AC)
Impulse withstand voltage U
imp
Operating frequency impulse withstand volt-
3 kV
DC power supply: Terminal 31, 32
Operating range of battery power supply
Current consumption (max.) 230 mA at 12 V DC
Voltage measuring inputs: Terminals 1-4 and 5-8
e
480 V AC L-L (277 V AC L-N)
50 ... 576 V AC L-L (333 V AC L-N)
Impedance of measuring input > 0.5 MΩ L-N
> 1.0 MΩ L-L
Single-phase, two-phase, or three-phase system
Measuring accuracy ± 0.25 %, value range ± 1 digit
i
Impulse withstand voltage U
imp
Operating frequency impulse withstand volt-
3 kV